SECTION: 26 32 15.00 ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH AUXILIARIES
 
Criteria

  1. UFGS 26 32 15.00 ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH AUXILIARIES
  2. JBLM 26 32 15.00  - ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH AUXILIARIES
Changes or Criteria Notes to Unified Facilities Guide Specifications (UFGS)
Paragraph # and Title (if any) Note to Designer Change Text
     
 
  
Design Requirements
 
  1. Generator controller shall be capable to interface the generator set to other power system equipment and network management systems using standard industry network communications. 
  2. New generator installation or replacement shall have raceway installed from generator to building EEDRS JACE Cabinet for future connection to remote monitoring system
  3. Manual Transfer Switch shall be 3-Way Switch equipped with interlocked breakers or controller to prevent cross-connecting power sources and color correct coded camlock receptacles allowing for safe isolated female connection points for load bank testing and portable generator male connection points.
  4. If Automatic Transfer Switch or Manual Transfer Switch to be utilized, a 3-Way Manual Transfer Switch must also be installed for safe annual testing requirements and for portable emergency generator connecting.
  5. Generator Emergency Shutdown shall be installed on the exterior of the generator enclosure per NEC Article 445.19.

 
Notes to Designers on Drawing Content
 
Standard Details
Only the DPW AHJ and/or electrical inspectors as appointees by the AHJ can override the design standards and codes.
 
Applicable Points of Contact
For all electrical inspections coordinate with:
Mr. Dwayne M. Lee
Senior Construction Control Representative/SCCR
CIB/ESD, Directorate of Public Works
Joint Base Lewis-McChord,WA 98433
Govt. Work Cell: (253)219-8969
Email: dwayne.m.lee.civ@army.mil
Design Standards