SECTION: 26 05 00.00 40 COMMON WORK RESULTS FOR ELECTRICAL
 
Criteria

  1. UFGS 26 05 00.00 40 COMMON WORK RESULTS FOR ELECTRICAL

Changes or Criteria Notes to Unified Facilities Guide Specifications (UFGS)
Paragraph # and Title (if any) Note to Designer Change Text
     
 
 
Design Requirements
  1. All cables shall be copper.
  2. EMT connection shall be compression type.
  3. Multiwire Branch Circuits not be permitted.

 
Notes to Designers on Drawing Content
 
Standard Details
Only the DPW AHJ and/or electrical inspectors as appointees by the AHJ can override the design standards and codes.
 