SECTION: 23 70 03.00 10 HEATING AND UTILITIES SYSTEMS, CENTRAL STEAM
Criteria
- Quality Assurance: EP 415-1-261, Volume 1 & EP 415-1-261, Volume 4
- UFGS SECTION 23 70 03.00 10 HEATING AND UTILITIES SYSTEMS, CENTRAL STEAM
- UFC 1-200-2 (High Performance and Sustainable Buildings Requirements)
- ASA IE&E Sustainable Design and Development Policy (Jan 17 2017)
Changes or Criteria Notes to Unified Facilities Guide Specifications (UFGS)
Paragraph # and Title (if any) | Note to Designer | Change Text |
1.2 SUBMITTALS | Delete reference to 01 33 29, unless it is incorporated in the specs and relevant to submittals in this section. | |
2.4.1 Condensate pumping Unit | Add to the paragraph: | Condensate Pumps: Shall be cast iron type, with duplex pumps. Seals shall be rated for temperature and application. |
2.4.1 Condensate Pumping Unit | Make the following selection (for condensate pumping unit): | duplex |
2.4.6 Steam Traps | Add to the paragraph: | Preferred Materials/Manufacturers for Steam Traps: Armstrong, Sarco (Keckley not acceptable). |
3.2.8 Pipe Expansion | Add to the paragraph: | Expansion: Pipe loops preferred. |
3.2.9.4 Pressure Reducing Valves | Add to the paragraph: | Preferred Materials/Manufacturers for Pressure Reducing Valves: Powers, Sarco. |
Design Requirements
Notes to Designers on Drawing Content
Standard Details
Applicable Points of Contact
Design Standards