SECTION: 23 54 16.00 10 HEATING SYSTEM; GAS-FIRED HEATERS
Criteria
- UFGS 23 54 16.00 10 HEATING SYSTEM; GAS-FIRED HEATERS
Changes or Criteria Notes to Unified Facilities Guide Specifications (UFGS)
Paragraph # and Title (if any) | Note to Designer | Change Text |
2.3.2 Indirect Fired Make-Up Heaters | Add the change text to the paragraph | Heat exchanger shall be stainless steel. |
2.4 Thermostats | Add the paragraph to the section | Infrared heaters with a heating input greater than 40 MBh shall be controlled by a standalone infrared heating control system or direct digital control (DDC) system. Individual black bulb sensors shall be installed in the space for each heater with a direct line-of-sight to the infrared heater being controlled. The control system shall have a set point range of 40 to 75 degrees F. No temperature adjustability shall be made available in the space. Control wiring required to complete the space temperature control system shall be included. |
Design Requirements
Notes to Designers on Drawing Content